TYPES AND CHARACTERISTICS
OF GENERATOR
The generators are classified into two types based on the
excitation method. The below figure shows types of generators.
Generally characteristics mean behavior of the particular
device with respect to the parameters. For generators the characteristics are
classified into two types shown below:
1. Magnetizing characteristics
2. Load characteristics
MAGNETIZING CHARACTERISTICS:
The characteristics which are obtained from the O.C.C curve are
named as Magnetizing characteristics. These characteristics are arrived from
emf equation of a generator by increasing or decreasing the flux value.
Eo = φZNP/60
Eo α φ
Hence
magnetizing characteristics are purely dependent on flux produced by the
winding when DC supply is given.
*As
If increases, φ increases then Eo increases, at certain point φ becomes
constant where Eo is said to be saturates.
2.LOAD CHARACTERISTICS:
The
load characteristics of DC generators drawn with terminal voltage Vt and load current IL
Due
to armature reaction the no load rated voltage Eo falls to E (known as Internal
characteristics) and further falls to terminal voltage Vt (known as External characteristics).
SEPARATELY EXCITED DC GENERATOR:
The generator which fails to self
excitation is excited by using prime mover such generators are named as
separately excited generators. The circuit diagram of this generator are
shown below:
In
these separately excited DC generators, EMF completely depends on flux φ. The
field regulator is necessary to control If.
Armature current Ia = IL
Terminal voltage V = Eg – IaRa + Brush
contact drop
Eg = V + IaRa
But Eg = φZNP/60A
Power delivered to the load
P = V*I
= (Eg – IaRa)*Ia
= EgIa – Ia^2 Ra
SHUNT GENERATOR:
* In shunt generator the winding is in
parallel to the armature. The induced EMF is same but field current If is different.
* The
load characteristics of DC generator is given below:
E = Vt + IaRa
As
per EMF equation E = φZNP/60
E α φ α Ia
If
the load increases IaRa drop increases by increasing Ia
IaRa = 1/Vt
* If
the voltage drop increases the terminal voltage decreases due to very small
armature resistance the Vt as load current changes from no-load to full
load is also very small. Hence DC shunt generator is called constant generator.
Armature current Ia = IL + Ish
Ish = V/Rsh
The general emf
Eg = V + IaRa + Brush
contact drop
Eg = V + ( IL + Ish)Ra + Brush
contact drop
Terminal voltage V = Eg – IaRa + brush
contact drop
SERIES GENERATOR:
In series generator the winding is in series
with the armature. The induced EMF is differ but If is same near winding. The load is
connected in parallel to the series generator.
Armature current Ia = Ise = IL
Where Ia = Armature current
Ise = Series
field current
IL = Load
current
Eg = V + Ia(Ra + Rse) + Brush
contact drop
The
equation for DC series generator is
E = Vt + Ia(Ra +Rse)
In
this generator the current Ia = Ise = IL (observe circuit diagrams)
Ia α Ise
Ise α φ
Φ α E
(From EMF equation)
From
the above three relations all are directly proportional to each other i.e. if
one of the parameter increases the other parameters are also increases. So the
internal characteristics increase in nature.
From
equations E = Vt + Ia(Ra + Rse)
Vt = E – Ia(Ra + Rse)
The
external characteristics are also increasing in nature as E increases but due
to the presence of IaRa drop the characteristics are take position
below the internal characteristics.
COMPOUND GENERATORS:
The
characteristics of compound generator depends on the type of generator i.e.
cumulative or Differential compound generator.
Cumulative compound:
Applying nodal
analysis
Ia = Ise = Ish + IL
Applying KVL
-V +Eg – IaRa – IseRse = 0
Eg = V + IaRa + IseRse + Brush
contact drop
Differential compound:
Apply nodal analysis
Ia = Ish + Ise (but Ise = IL)
Ia = Ish + IL
IL = Ia – Ish
Apply KVL
-V
+ Eg – IaRa – IseRse = 0
Eg = V + IaRa + IseRse + Brush
contact drop The shunt
current Ish = Eg/Rsh = (V + IseRse)/Rsh
Total flux φ = φsh + φse
Φ α I
Ian α Isa
* If the voltage drop increases the IL increasing and flux also increases then generator is called UNDER COMPOUNDED.
* If
Vt drop is more when compared to other drops
while flux
increases then generator is called OVER COMPOUNDED.
* When
Vt and Eo are same then generator is named as
FLAT or LEVEL COMPOUNDED.
No comments:
Post a Comment